Water System


Segments   

    1-) Water intake to facility and water conditioning system

    2-) Deionized water unit

    3-) Distiled water unit



1-) Water intake to facility and water conditioning system   

Capacity:   

    Capasity of water conditioning system: 5000L/hour

    Capacity of water storage: 100 tons of water


Exist Values:   

Conductivity:    100 µs

Hardness:    max 0,57 F

pH:    5 -'7

Chlorine:    0,005 mg/l

Evaporation remnant weight:    <0,005%



2-) Deionized water unit   
  
Capasity:   

    3 tons/hour capacity

Attributes:   

    Scade controlled

    1st step: Membrane filtration.

    2nd step: EDI (electrodeionizer)

Exist Values:   

Conductivity:    <1,3 µs @ 25 C

Hardness:    0 F

pH:    5 - '7

TOC (total organic carbon):     500 ppm max

Microbial weight    <100 cfu/ml



A building: Betalactam product manufacturing building deionized water unit.   
 
Attributes:   


    2 tons capacity stock tank

    Pasterisation unit

    PLC controlled otomation


B building: Non-Betalactam product manufacturing building deionized water unit.   

Attributes:   


    3 tons capacity stock tank

    Pasterisation unit

    PLC controlled automation


C building: Biocidal product manufacturing building deionized water unit.   
 
Attributes:   


    Reverse osmos water system with 1 tons of water stock capacity

    1 tons capacity deionized stock tank, deionize water line and automation.

  
D building: Pilot manufacturing building deionized water unit.   

Attributes:   


    Reverse osmos water system with 250 liter/hour  water capacity

    500 liter capacity deionized stock tank, pasifization unit and automation.



3-) Distile water unit   

Capasity:   

    750 l/hour capacity


Attributes:   

    Scade controlled distillation unit


Exist Values:   

Conductivity:    <1 µs @ 250C

pH:    5 - '7

TOC (total organic carbon):     500 ppm max

Bacterial endotoxins    <0,25 IU/ml


A building: Betalactam product manufacturing building distile water unit.   
 
Attributes:  
 

    1 tons capacity, heating jacket,(+) electronic heater stock tank

    Distile water line and PLC controlled automation


B building: Non-Betalactam product manufacturing building distile water unit.   
 
Attributes:   

 
    2 tons capacity, heating jacket,(+) electronic heater stock tank

    Distile water line and PLC controlled automation